Standard: IEC 60255

A
A

Range: 0.05 - 1.5

Waktu Trip

4.280 s

Kelipatan Arus

5.00×

I/Is

Zona Trip

Thermal / Long-time

Curve Visualization

Current Multiple (I/Is)Trip Time (s)1235102030501000.111010010005.00× = 4.280 sIEC Standard Inverse Curve
Kurva
Titik Terhitung

Formula Reference

IEC 60255 Standard Formula

t=TMS×
k
(I/Is)α−1

Where: t = trip time (s), TMS = Time Multiplier Setting, I = fault current, Is = pickup current

IEEE C37.112 Standard Formula

t=TD×
[
A
(I/Is)p−1
]
+B

Where: t = trip time (s), TD = Time Dial, I = fault current, Is = pickup current

IEC 60255 Equation Constants

Tipe Kurvakα
IEC standard inverse curve0.1400.020
IEC very inverse curve13.51
IEC extremely inverse curve802
IEC long time standard inverse curve1201

IEEE C37.112 Equation Constants

Tipe KurvaABp
IEEE moderately inverse curve0.05150.1140.02
IEEE very inverse curve19.610.4912
IEEE extremely inverse curve28.20.12172.0

Tentang Relay IDMT

Relay IDMT beroperasi dengan penundaan waktu.